Chapter 9
9.7 Examples
9.7.1 Example
Consider a closed loop unit feedback system operating initially under Proportional Control where the process transfer function G(s) is as follows:
Part 1. Find the stability range, and assume the operating gain such that the Gain Margin = 2.
Part 2. Next, replace the gain with a parallel structure of the PID Controller, with the settings for the Derivative Time Constant τd=2τd=2 seconds and for the Integral Time Constant τi=10τi=10seconds. Fine-tune the PID Controller by simulations.
9.7.2 Example
Consider again the system from Example 7.3.17 and Example 8.7.14, only now the P+Rate Feedback and PI+ Rate Feedback are replaced with a series configuration of a PID Controller, as shown.
G(s) process transfer function remains the same as before:
G(s)=1s2+7s+5G(s)=1s2+7s+5
All gain values are kept exactly the same as you determined them in those two previous examples:
Kp=40.78Kp=40.78, Kd=0.0245Kd=0.0245 and Ki=0.7Ki=0.7. How different will be the PID system closed loop transfer function from the P+Rate and PI+Rate? How different will the system step response be? Will the difference be significant? Briefly justify your answers.